What is there to see?
Within this page you will find information pertaining to LaserPure and ICE water-to-water heat exchangers, PolarPure closed-loop water chillers and the LaserPure 5i water-to-air heat exchanger. You may also contact Technical Support for more information. For price quotes please call, fax, or E-Mail us. Our contact information can be found at the bottom of this page for your convenience. Heat Exchangers Available for Purchase
Water-to-Water Heat Exchangers LaserPure-20 LaserPure-40 LaserPure-60 ICE Water-to-Air Heat Exchanger LP-5i Closed-Loop Water Chillers PolarPure 6 PolarPure 12 PolarPure 18 Specifications
| LaserPure 20 | LaserPure 40 | LaserPure 60 | Cooling capacity at maximum plant flow | 20 kW | 40 kW | 60 kW | deltaT @ maximum cooling capacity, 8 GPM (LP20), 10 GPM (LP 40), 15 GPM (LP 60) plant flow | 4oC | 5oC | 5oC | Maximum plant static pressure | 100 PSI | 100 PSI | 100 PSI | Plant water temperature range | 5-30oC | 5-30oC | 5-30oC | Plant water quality | Glycol OK. Not designed for seawater. | Glycol OK. Not designed for seawater. | Glycol OK. Not designed for seawater. | Laser loop flow | 2 - 3 GPM nominal 5 GPM max | 5 - 7 GPM nominal 15 GPM max | 6 - 8 GPM nominal 15 GPM max | Maximum laser loop return temperature | 70oC | 70oC | 70oC | To-Laser temperature regulation | ± 1oC | ± 1oC | ± 1oC | Power Requirements (Max. operating load, both models) | 208/220/240 VAC, 50/60 Hz 7.1 A @ 60 Hz 7.8 A @ 50 Hz | 208/220/240 VAC, 50/60 Hz 7.1 A @ 60 Hz 7.8 A @ 50 Hz | 208/220/240 VAC, 50/60 Hz 7.1 A @ 60 Hz 7.8 A @ 50 Hz | Interlock contact rating | 5 A @ 28 VAC | 5 A @ 28 VAC | 5 A @ 28 VAC | Interlock contact condition: | | | | normal | closed | closed | closed | If reservoir level falls below ``Very Low" | open | open | open | If laser loop return temp. exceeds 77 +/- 3oC | open | open | open | Laser loop sensitivity | 500 KΩ-cm to 2 MΩ-cm | 500 KΩ-cm to 2 MΩ-cm | 500 KΩ-cm to 2 MΩ-cm | Laser loop water quality | no additives allowed | no additives allowed | no additives allowed |
For contacts to open, power must be applied and pump must be on. Note: CSA Certifiable
| ICE | LP-5i | | PLANT SIDE WATER | | | | Cooling capacity | 26 kW @ max flow | 5 kW max @ 2 GPM @ 40oC ambient | | Static Pressure | 90 PSI max | N/A | | Temp | 5-30oC | N/A | | Temp Delta w/max flow minimum | 40oC 5oC | N/A | | Flow | 2-8 GPM | N/A | | Quality | Tap water or any closed loop water cooling system. | N/A | | Resistivity | 50 KΩ-cm to 2 MΩ-cm recommend: > 100 MΩ-cm | N/A | | pH | 6 - 8 | N/A | | Hardness | <100 mg/L or 100 ppm calcium | N/A | | Particulate Size | <200 µm | N/A | | Additives | | N/A | | LASER SIDE WATER Into laser | | | | Water Temp | 35oC max | | | Water Flow nominal min/max | 2.5 - 3 GPM 1.8 / 3.5 GPM | 2 GPM 2.5 GPM max | | Water Pressure min/max | 22 / 40 PSI | | | Temp Regulation | ± 1oC | None | | Loop Resistivity | 50 KΩ-cm to 2 MΩ-cm | Optional ext. filter deionizing/ de-oxygenating | | Water Temp Rtn | 60oC max | 68oC @ 2 GPM @ 40oC Ambient | | Additives | None | None | | POWER | | | | Requirements | 208 VAC ± 10% 50/60 Hz 3 PH w/GND WYE No Neutral | 100 VAC, 60 Hz 230 VAC, 50/60 Hz | | Operating Load | ----- | 5.5 A @ 110 VAC 3.5 A @ 230 VAC | | Interlock Contact Rating | ----- | 10 A @ 120 VAC 10A @ 28 VDC | | Ambient Air | N/A | 40oC max | | | LASER HEAT LOAD | | | | Innova 70C | 20 kW | | | Innova 90C | 20 kW | | | Innova 90C FreD | 20 kW | | | Innova 300C | 24 kW | | | Innova 300C MotoFreD | 24 kW | | | StarC | 20 kW | | | | | | |
[Back to Top]
Laser Innovations 1150 E. Main Street Santa Paula CA 93060 Tel (805) 933-0015 Fax (805) 933-0042 E-mail: information@coherentlaser.com
|